Short-Circuit Power of a Synchronous Generator

Short-Circuit Power of a Synchronous Generator ​

The short-circuit power of a synchronous generator indicates its capacity to deliver power during a short circuit or fault condition. This concept is often referred to as fault MVA or short-circuit MVA. Understanding this parameter is essential for assessing generator strength during faults and for sizing protective devices like circuit breakers, as well as evaluating system stability.

 

Short-Circuit Power Calculation

The short-circuit power (or fault MVA) is derived from the voltage at the generator terminals and the subtransient reactance, which reflects the generator’s impedance during fault conditions. This value indicates the maximum power (in MVA) the generator can theoretically supply if a short circuit occurs at its terminals.

The short-circuit power Ssc can be calculated using the formula:

\[{{S}_{sc}}=\frac{{{V}_{nom}}}{{{X}^{”}}}\]

Where:

  • Ssc = Short-circuit power (in MVA)
  • Vnom = Nominal terminal voltage of the generator
  • X′′ = Subtransient reactance of the generator (in per-unit or ohms)

Significance

The short-circuit power reveals the maximum current the generator can deliver during the initial moments of a fault.

It is vital for designing protective equipment capable of handling high fault currents.

This value aids in determining the fault current by dividing the short-circuit power by the system voltage at the fault point.

Designing a Synchronous Generator for Fault Power

To construct a synchronous generator that can withstand fault power, several key factors must be taken into account:

  1. Specify Key Design  Parameters

  • Nominal Power Rating: Align the generator’s nominal power rating with operational needs.
  • Short-Circuit Power: Ensure the generator is designed to endure this fault power without damage.
  • Subtransient Reactance: This parameter is crucial for assessing fault current during the initial fault cycles.
  1. Calculate Fault Current

The fault current is critical for design. It can be calculated using the given short-circuit power. The formula to calculate fault current Ifault is:

         \[{{I}_{fault}}=\frac{{{S}_{sc}}}{\sqrt{3}\cdot {{V}_{nom}}}\]                                                      

  1. Determine Subtransient Reactance

The subtransient reactance limits the fault current during the subtransient period (typically the first 0.1-0.3 seconds). The relationship between short-circuit power and subtransient reactance helps estimate 𝑋’’

\[{{X}^{”}}=\frac{V_{nom}^{2}}{{{S}_{sc}}}\]

  1. Thermal Design for Fault Duration

Ensure the generator’s thermal capacity can handle the heat generated by the fault current for a specified duration without damaging insulation or windings.

  1. Mechanical Strength

The generator must be robust enough to withstand the electromechanical forces caused by the fault current. This includes proper design of the rotor and stator to handle the stresses during faults.

  1. Cooling System Design

A reliable cooling system is essential due to the significant heat generated during faults. It must prevent overheating during peak temperature rises.

  1. Protection System Coordination

Ensure the protection system can clear faults swiftly, including:

Fast-acting relays and circuit breakers.

Overcurrent protection to trip within the fault period.

  1. Material Selection

High-quality conductors and insulation materials must be chosen to withstand expected temperatures and mechanical stresses.

  1. Simulation and Testing

Conduct simulations of fault conditions to validate the design’s fault-handling capacity.

Perform fault tests to ensure the generator can manage fault power without sustaining damage.

Mechanical and Electrical Design Considerations for Switchgear Testing

Synchronous generators are also used for switchgear testing. Key considerations include:

Electrical Design

  • Reactance: Testing alternators require low reactance (less than 5%) to permit high currents during short circuit tests. This is achieved by:
    • Reducing the nuber of stator conductors.
    • Using open slots to minimize magnetic flux leakage.

Mechanical Design

  • Conductors and Windings: High currents impose significant mechanical forces, necessitating robust support systems.
  • Foundations: The structure must handle high torque stresses from rapid deceleration during tests.

Methods to Increase Output

  • External Reactance: Reducing external circuit reactance maximizes test output.
  • Initial Voltage: Increasing the initial voltage enhances recovery voltage and test currents.
  • Additional Excitation: Applying extra excitation during tests can sustain or boost current levels.

Conclusion

Designing a synchronous generator to manage fault power necessitates careful consideration of subtransient reactance, thermal and mechanical durability, and effective cooling. Proper coordination of protection systems is crucial to ensure the generator operates effectively under extreme conditions.

Recent articles

Data to be checked when replacing the AVR